| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5225-5GD41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection. It has a maximum rated operational current of 250A and a rated operational voltage of up to 690V AC.
The circuit breaker offers a breaking capacity of 35kA at 480V according to UL 489 standards and 85kA at 240V according to IEC 60947 standards. The overcurrent release is of type TM210 with LI protection function. It supports N conductor protection at 100%.
Designed for DIN rail mounting, this breaker has a mechanical service life of typically 20,000 switching cycles. It is also listed with HACR Type approval, indicating suitability for Heating, Air Conditioning, and Refrigeration applications.
Key electrical specifications include a maximum power loss of 58W. The operational current is rated at 250A up to 50°C, decreasing slightly at higher temperatures.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690V AC at 50/60Hz.
The breaking capacity according to UL 489 at 480V is 35kA.
The permanent assigned current rating (Iu) is 250A, and the maximum rated operational current of the frame size is also 250A.
This circuit breaker has 4 poles.
This circuit breaker is designed for DIN Rail mounting.