| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
The Siemens 3VA5222-7GD41-0AA0 is a 4-pole molded case circuit breaker from the 3VA series, designed for system protection. It has a maximum rated operational current of 250A and a permanent rated current (Iu) of 225A.
This circuit breaker offers a breaking capacity of 100kA at 480V according to UL 489 standards, and 85kA at 415V according to IEC 60947. The overcurrent release is type TM210 with LI protection function. It supports 100% N-conductor protection.
With a mechanical service life of typically 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V, this breaker is built for durability. It is designed for DIN rail mounting and has an insulation voltage of 800V and a maximum rated operational voltage of 690V AC.
Key electrical specifications include a maximum power loss of 51.2W. The adjustable short-circuit protection (Ii) ranges from 2250A to 2250A. It is UL listed and meets CCC, CE, CSA, and EAC approval agency standards.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The permanent rated current (Iu) is 225A, and the operational current at 40°C is also 225A.
The breaking capacity (Icu) is 100kA at 480V according to UL 489, and 85kA at 415V according to IEC 60947.
The maximum rated operational voltage (AC) is 690V, and the insulation voltage (Ui) is 800V.
This circuit breaker has 4 poles.
It supports DIN rail mounting.
Yes, it is RoHS3 Compliant.