This Siemens 3VA5222-5GC41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection. It features a current rating of 225A and a maximum operational voltage of 690V AC.
The circuit breaker provides LI protection with an overload setting (Ir) fixed at 225A and an adjustable short-circuit setting (Ii) ranging from 1125A to 2250A. It boasts a breaking capacity of 35kA at 480V according to UL 489 standards, and 55kA at 415V according to IEC 60947 standards.
With a mechanical service life of 20,000 cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It is designed for DIN rail mounting and features a lever actuator. The N-conductor protection is rated at 100%.
Key electrical specifications include a maximum power loss of 51.2W and an active power loss per pole of 17.07W at rated current. The insulation voltage is rated at 800V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The permanent current rating (Iu) is 225A, and the operational current at 40°C is also 225A.
The maximum rated operational voltage with AC 50/60Hz is 690V.
The breaking capacity (Icu) is 55kA at 415V and 7kA at 690V according to IEC 60947. According to UL 489, the breaking capacity is 35kA at 480V.
It offers LI protection, with a fixed overload setting (Ir) of 225A and an adjustable short-circuit setting (Ii) from 1125A to 2250A.
This circuit breaker has 4 poles.
The mounting type is DIN Rail.