This Siemens 3VA5222-6GD41-0AA0 is a molded-case circuit breaker designed for system protection. It features a 4-pole configuration and a rated operational current of 225A, with a maximum rated operational voltage of 690V AC and 1000V DC.
The circuit breaker has a breaking capacity of 65kA at 480V according to UL 489 standards and 70kA at 415V according to IEC 60947 standards. The overcurrent release is type TM210 with LI protection functions. It supports N-conductor protection at 100% and is HACR Type compliant.
With a mechanical service life of typically 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It is designed for DIN rail mounting.
Key electrical specifications include a maximum power loss of 51.2W and an active power loss of 17.07W per pole at rated current in hot operating state. The insulation voltage is rated at 800V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The permanent current rating (Iu) is 225A, and the operational current at 40°C is also 225A.
The maximum rated operational voltage with AC 50/60Hz is 690V, and with DC it is 1000V.
The breaking capacity according to UL 489 is 65 kA at 480V.
This circuit breaker has 4 poles.
The mounting type is DIN Rail.