| Category | |
| Manufacturer Name | |
| Applications | |
| Approval Agency | |
| Current | |
| Efficiency | |
| Features | |
| Frequency | |
| Input Voltage | |
| Isolation | |
| Mounting Type | |
| Number of Outputs | |
| Operating Temperature | |
| Power (Watts) | |
| Storage Temperature | |
| Temperature Coefficient | |
| Type | |
| Voltage |
The Artesyn Embedded Power MP6-3Q-LLE-0M is a high-performance AC/DC converter designed for demanding applications. This enclosed unit delivers up to 800W of power and features a 5V output, suitable for ITE (Commercial) and Medical applications.
Key electrical specifications include a wide input voltage range of 85-264 VAC and 120-350 VDC, with a typical efficiency of 85% and a power factor of 0.99. It offers features such as adjustable output, power factor correction (PFC), and remote On/Off control. The converter supports chassis mounting and includes overload protection and remote sense capabilities on outputs rated greater than 2A.
Environmental and safety standards are met with approvals including CB, CE, CSA, UL, and VDE. The operating temperature range is -20°C to 50°C, with derating to 50% at 70°C. It also offers a low leakage option for medical applications, meeting CISPR 22 and EN55022 Class B conducted and radiated EMI standards. The unit is designed with forced air cooling and a field-replaceable fan.
This model provides multiple outputs and supports features like current sharing on outputs rated 10A or greater, and margining on single output modules. It also includes status indicator LEDs for input and global DC OK signals, along with global and individual module inhibits/enables.
The input voltage range is 85-264 VAC or 120-350 VDC.
The operating temperature range is -20°C to 50°C (start at 0°C), with derating to 50% at 70°C.
It is an enclosed chassis mount unit with forced air cooling via an internal DC fan.
The converter provides four outputs: 24V, two 12V outputs, and a 5V output. The 5V output is rated at 2A.
Yes, it has active power factor correction with a typical power factor of 0.99, meeting EN61000-3-2.
It is approved by CB, CE, CSA, UL, and VDE.
The hold-up time is 20 ms minimum, independent of input VAC.