| Category | |
| Manufacturer Name | |
| Applications | |
| Approval Agency | |
| Current | |
| Efficiency | |
| Features | |
| Frequency | |
| Input Voltage | |
| Isolation | |
| Medical Grade | |
| Mounting Type | |
| Number of Outputs | |
| Operating Temperature | |
| Overload Protection | |
| Power (Watts) | |
| SVHC Present | |
| Storage Temperature | |
| Temperature Coefficient | |
| Type | |
| Voltage |
The Artesyn Embedded Power MP6-2Q-4LN-4NE-00 is a versatile AC DC converter with a power rating of 800W. It is designed for chassis mounting and offers features such as adjustable output, power factor correction (PFC), and remote on/off capability, along with a universal input.
This converter operates within an input voltage range of 85-264 VAC and 47-440 Hz frequency, providing an efficiency of typically 85%. It supports multiple outputs, including 5V, and is suitable for applications in ITE (Commercial) and Medical sectors. The unit meets various safety and compliance standards including UL, CSA, CE, and VDE.
Key electrical specifications include a typical power factor of 0.99, meeting EN61000-3-2 harmonic distortion compliance. It also features standard CISPR 22 EMI filtering and offers a low leakage option for medical applications, with leakage current at a maximum of 300 µA @ 240 VAC. The operating temperature range is -20°C to 50°C, with derating at higher temperatures.
Designed for robust performance, the MP6-2Q-4LN-4NE-00 includes overload protection, remote sense on outputs greater than 2A, and global inhibit/enable functions. It is cooled by an internal DC fan, which is field replaceable, and offers a 2-year warranty.
The input voltage range is 85-264 VAC or 120-350 VDC, with a frequency range of 47-440 Hz.
The converter provides five outputs: 24V, 12V, two 15V, and two 5V rails. The main 5V output is rated at 10A.
The operating temperature range is -20°C to 50°C, with derating to 50% at 70°C. With the rear air option, the maximum is 40°C.
The unit meets UL1950, CSA22.2 No. 234 Level 5, IEC950 Class 1, VDE EN60950, and BABT compliance to EN 60950/BS 7002. It carries CE marking and a CB certificate.
Yes, remote sense is available on all outputs rated greater than 2A, and current sharing is supported on all outputs rated 10A or greater.
Overload protection is provided on all outputs. The unit also includes global and individual module inhibit/enable, input OK signal, global DC OK signal, and fan fail signal.
The efficiency is 85% typical, with a datasheet range of 70-80% typical at full case load.