| Category | |
| Manufacturer Name | |
| Applications | |
| Approval Agency | |
| Current | |
| Efficiency | |
| Features | |
| Frequency | |
| Input Voltage | |
| Isolation | |
| Medical Grade | |
| Mounting Type | |
| Number of Outputs | |
| Operating Temperature | |
| Power (Watts) | |
| Storage Temperature | |
| Temperature Coefficient | |
| Type | |
| Voltage |
The Artesyn Embedded Power MP6-1W-1W-1W-4NE-4NN-00 is an 800W enclosed AC DC converter designed for ITE (Commercial) and Medical applications. This unit features a chassis mount type and provides 7 outputs, including a 15V output with 8A current capability.
Key electrical specifications include an input voltage range of 85-264 VAC and 120-350 VDC, with a frequency range of 47-440 Hz. It boasts a typical efficiency of 70-80% at full load, with a specific rating of 85% provided. The power factor is typically 0.99, meeting EN61000-3-2 standards. Special features include adjustable outputs, power factor correction (PFC), remote on/off capability, and universal input.
Environmental and safety compliance is met with UL, CSA, IEC, VDE, BABT, and CE Mark certifications. The operating temperature range is -20°C to 50°C, with derating to 50% at 70°C. For medical applications, a low leakage option is available, reducing leakage current to 300 µA max. @ 240 VAC.
The unit is designed for robust performance with features like overload protection, remote sense on outputs rated greater than 2A, and input OK signal. It also includes global and individual module inhibits/enable functions. Cooling is managed by an internal DC fan or an optional customer-provided air system.
The input voltage range is 85-264 VAC or 120-350 VDC at 47-440 Hz.
The operating temperature range is -20°C to 50°C (with derating to 50% at 70°C). With rear air option maximum is 40°C.
It has 7 outputs: three 48V, one 15V, and two 5V.
Typical efficiency is 70-80% at full load, with a separate efficiency rating of 85%.
Yes, power factor correction with typical value 0.99 meeting EN61000-3-2 harmonic distortion limits.
It carries UL1950, CSA22.2 No. 234 Level 5, IEC950 Class 1, VDE EN60950, BABT compliance to EN60950/BS7002, CB certificate, and CE marking.
The holdover storage time is 20 ms minimum, independent of input VAC.