This Schurter Inc. 4430.387 is a thermal circuit breaker with a 2-pole configuration, suitable for various industrial applications. It offers a rated current of 5A and a voltage rating of 240VAC, with a DC rating of 60VDC. The breaker type is thermal, providing reliable overload protection.
The device is designed for panel mounting, ensuring easy integration into control panels and equipment. It features a rocker actuation type for user interaction. The circuit breaker has a conditional short circuit capacity of 1 kA at 240VAC and a short circuit capacity of 300A at 240VAC.
Key specifications include a degree of protection of IP40 on the front side, a dielectric strength of 4kVAC, and an insulation resistance greater than 100 MΩ at 500VDC. The operating temperature range is -10°C to 55°C, making it suitable for a variety of environments. Mechanical lifetime is rated at 50,000 switching cycles.
The circuit breaker is rated for 240VAC and 60VDC.
The circuit breaker is panel mount with a rocker actuator.
The allowable operating temperature range is -10°C to 55°C.
The conditional short circuit capacity Inc is 1kA at 240VAC. The short circuit capacity Icn is 300A for currents ≥3A at 240VAC.
The circuit breaker has 2 poles.
The dielectric strength is 4kVAC.
The circuit breaker is approved under CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, and UL1077.