| Category | |
| Manufacturer Name | |
| Accessory Type | |
| For Use With |
This Siemens 3VA9233-0JJ22 is an accessory terminal block, specifically a wire connector, designed for integration with the 3VA5 250 circuit breaker series.
It facilitates connections for both copper and aluminum stranded conductors, accommodating sizes from a minimum of 4 AWG up to 300 kcmil (or 25 mm² to 150 mm² according to IEC standards). The required stripped length for connections ranges from 1 to 2 inches (26 to 51 mm).
Installation involves specific tightening torques to ensure secure connections. For copper cables, the recommended torque is 275 lb-in (UL) or 31.1 Nm (IEC) for stranded and finely stranded conductors within the specified ranges. The permissible conductor temperature according to UL 486A-486B is 75 °C.
This accessory is part of the SENTRON product line, offering reliable connectivity solutions for electrical distribution systems.
The accessory type is a Terminal Block, specifically a wire connector.
This accessory is designed for use with the 3VA5 250 circuit breaker series.
The minimum connectable conductor cross-section for copper cable (stranded) according to IEC is 25 mm².
The maximum connectable conductor cross-section for aluminum cable (stranded) according to IEC is 150 mm².
The stripped length required for connections according to IEC is 26 mm to 51 mm.
The tightening torque for stranded copper cables (25-150 mm²) is 31.1 Nm.
The permissible temperature of the connectable conductor according to UL 486A-486B is 75 °C.
The maximum connectable conductor cross-section for copper cable (stranded) according to UL is 300 kcmil.
The tightening torque for finely stranded copper cables (4 AWG - 300 kcmil) is 275 lb-in.