This Siemens 3VA6 molded-case circuit breaker, part number 3VA6325-5JQ41-0AA0, is a 4-pole unit designed for system protection. It has an operational current rating of 250A and offers a breaking capacity of 35kA at 480V according to UL standards, and up to 85kA at 240V per IEC standards.
The breaker utilizes an ETU560 overcurrent release with LSIG (Line, Short-circuit, Delayed short-circuit, Ground fault) protection functions. Adjustable settings include overload protection from 100A to 250A, short-circuit protection (Isd) from 0.6 to 10 times the rated current, and instantaneous short-circuit protection (Ii) from 1.5 to 12 times the rated current. Ground fault protection is adjustable from 0.2 to 1 times the rated current, with a time delay option.
With a rated insulation voltage of 600V, this circuit breaker is suitable for various applications. It supports communication functions and is HACR Type rated. The mechanical service life is typically 15,000 switching cycles, with electrical endurance ratings varying by voltage and load conditions.
Mounting is designed for DIN rail installation. The breaker has a maximum power loss of 27.3W.
The operational current rating is 250A at temperatures up to 70°C. Overload protection is adjustable from 100A to 250A.
The breaking capacity is 35kA at 480V according to UL standards, and 85kA at 240V, 55kA at 415V, and 5kA at 690V according to IEC standards.
The ETU560 overcurrent release includes LSIG protection functions: Line, Short-circuit (delayed), Instantaneous short-circuit, and Ground fault.
The rated insulation voltage (Ui) is 600V.