| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5280-5ED31-2AA0 is a 3-pole molded-case circuit breaker designed for system protection. It operates with a rated insulation voltage of 800V and a rated operating voltage of up to 690V AC or 750V DC.
The breaker has a nominal current rating of 80A at 40°C, with a maximum power loss of 20W. It features a TM210 overcurrent release with LI protection function. The short-circuit breaking capacity (Icu) is 55 kA at 415V and 7 kA at 690V, with a making capacity (Icm) of 121 kA at 415V.
According to UL 489 standards, it has a current breaking capacity of 35 kA at 480V and is designated as HACR Type. The breaker is 100%-rated and mounts via DIN rail. It has a mechanical service life of 20,000 operating cycles and an electrical endurance of 8,000 cycles at 380/415V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker is 690 V at AC and 750 V at DC.
The operational current at 40°C is 80 A.
The maximum short-circuit current breaking capacity (Icu) is 55 kA at 415 V and 7 kA at 690 V. The operating short-circuit current breaking capacity (Ics) is also 55 kA at 415 V and 7 kA at 690 V.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.
The mounting type is DIN Rail.