| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
This Siemens 3VA5220-7EF32-0AA0 is a 3-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It operates at a rated voltage of 690V AC and has a maximum breaking capacity of 100kA at 480V AC according to UL 489 standards.
The breaker has a nominal operational current of 200A at 40°C, with derated values at higher temperatures. It features an adjustable overload protection from 160A to 200A and short-circuit protection adjustable from 5 to 10 times the nominal current. The overcurrent release is of type TM240 with LI protection function.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 480V and 4,000 cycles at 690V, this circuit breaker is built for durability. It has a maximum power loss of 43W and a net weight of 2.252 kg. The unit is designed for DIN rail mounting and features a lever actuator.
Compliance includes CCC, CE, CSA, and UL489 approvals. It is also listed as HACR Type according to UL 489. The breaker is RoHS3 compliant, has an MSL of 1, and is REACH unaffected.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operational voltage for this circuit breaker at AC is 690 V.
The breaking capacity current according to UL 489 at 480 V is 100 kA.
The operational current at 40 °C is 200 A.
This circuit breaker has 3 poles.
This circuit breaker supports DIN Rail mounting.
Yes, this circuit breaker is RoHS3 Compliant.