| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Connection Type | |
| Current Rating (Amps) | |
| Depth | |
| Dimensions | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Temperature Rating | |
| Trip Range | |
| Voltage Rating | |
| Width |
This Siemens SENTRON 3VA5 series molded-case circuit breaker, part number 3VA5220-5EC36-0AA0, is designed for system protection. It features a 3-pole configuration and a rated operational current of 200A at 40°C, with a maximum operating voltage of 690V AC.
The circuit breaker has a breaking capacity of 35kA at 480V according to UL 489 standards and 55kA at 415V according to IEC 60947. The overcurrent release is of type TM230 with LI protection function. It is suitable for HACR Type applications.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It has a compact design with dimensions of 105mm width, 83mm depth, and 185mm height, suitable for DIN rail mounting. The connection type is aluminum lug on both line and load sides.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 200A at 40°C.
The rated insulation voltage is 800V, the maximum rated operational voltage with DC is 750V, and the rated operating voltage at AC is 690V.
The breaking capacity according to UL 489 is 35kA at 480V, and according to IEC 60947, it is 55kA at 415V.
It uses a Thermal Magnetic trip type.
The dimensions are 105 mm width, 83 mm depth, and 185 mm height.