| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This Siemens 3VA5220-6EF41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It offers a permanent rated current of 200A, with operational current ratings that vary slightly with ambient temperature, from 200A at 40°C down to 176A at 70°C.
The breaker operates at a maximum rated operational voltage of 690V AC and 1000V DC, with an insulation voltage of 800V. It provides overload protection with an adjustable response value (Ir) from 160A to 200A and short-circuit protection (Ii) adjustable from 5 to 10 times the rated current.
Key electrical performance includes a breaking capacity (Icu) of 100 kA at 240V, 70 kA at 415V, and 10 kA at 690V according to IEC standards. Under UL 489, the breaking capacity is 65 kA at 480V and 25 kA at 600Y/347V. The circuit breaker has a mechanical service life of 20,000 cycles and an electrical endurance of up to 8,000 cycles at 380/415V.
Designed for DIN rail mounting, this HACR Type circuit breaker is suitable for Heating, Air Conditioning, and Refrigeration applications. It features a TM240 overcurrent release and LI protection function. Communication and other measurement functions are not available on this model.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V AC at 50/60 Hz and 1000 V DC.
The permanent rated current is 200 A, and the operational current at 40°C is also 200 A.
The breaking capacity according to IEC 60947 is 70 kA at 415 V and 10 kA at 690 V. According to UL 489, it is 65 kA at 480 V.
This circuit breaker is designed for DIN rail mounting.
The RoHS status is RoHS3 Compliant.