| Voltage Rating |
This Siemens 3VA5220-7GD41-0AA0 is a 4-pole molded-case circuit breaker from the SENTRON series, designed for system protection. It has a maximum rated operational current of 250A and a permanent rated current (Iu) of 200A, with operational current ratings specified up to 70°C.
The circuit breaker offers a high breaking capacity, rated at 100kA at 480V according to UL 489 standards, and 85kA at 415V according to IEC 60947. It features TM210 overcurrent release with LI protection function and adjustable short-circuit protection settings (Ii min/max 2000A).
Designed for DIN rail mounting, this unit has a mechanical service life of typically 20,000 switching cycles. It operates with an insulation voltage of 800V and a maximum rated operational voltage of 690V AC (50/60Hz) or 1000V DC. The N-conductor protection is rated at 100%.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V AC at 50/60 Hz and 1000 V DC.
The breaking capacity according to UL 489 is 100 kA at 480 V, and according to IEC 60947 it is 85 kA at 415 V and 10 kA at 690 V.
The permanent rated current (Iu) is 200 A, and the operational current at 40°C is also 200 A.
This circuit breaker is designed for DIN rail mounting.
This component is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1.