| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
This Siemens 3VA5 molded-case circuit breaker, part number 3VA5160-6EF32-0AA0, is a 3-pole unit designed for line protection and system protection applications. It features an operational current rating of 60A at 40°C, with derated values at higher temperatures.
The breaker provides a breaking capacity of 65kA at 480V according to UL 489 standards, and 10kA at 690V according to IEC 60947. It is equipped with a TM240 overcurrent release with LI protection function. The rated insulation voltage is 800V, with a maximum operational voltage of 690V AC and 500V DC.
Mechanical specifications include a typical service life of 20,000 cycles. The unit has dimensions of 140mm height, 76.2mm width, and 76.5mm depth. It is designed for DIN rail mounting.
Compliance includes UL489 and CCC approvals, and it is designated as HACR Type. The breaker has a maximum power loss of 15.4W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 60A at 40°C, decreasing to 54A at 70°C.
According to UL 489, the breaking capacity is 65kA at 480V. According to IEC 60947, it is 10kA at 690V.
The rated operating voltage at AC is 690V, and the maximum operational voltage with DC is 500V.
The overcurrent release offers LI protection.
The dimensions are 140mm in height, 76.2mm in width, and 76.5mm in depth.
Yes, it is designed as a Heating, Air Conditioning, and Refrigeration (HACR) Type circuit breaker according to UL 489.