| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
This Siemens 3VA5160-5ED32-0AA0 is a molded-case circuit breaker from the 3VA5 UL frame 125 series, designed for system protection applications. It features a 3-pole configuration and a rated operational current of 60A at 40°C, with a derated current of 54A at 70°C.
The circuit breaker offers a breaking capacity of 35kA at 480V according to UL 489 standards and 55kA at 415V according to IEC 60947 standards. It is equipped with TM210 overcurrent release and LI protection function.
Designed for easy installation, this unit features DIN rail mounting. Its mechanical service life is rated at a typical 20,000 switching cycles, with electrical endurance varying based on voltage and load conditions, such as 8,000 cycles at 380/415V AC-1.
Key electrical specifications include a rated insulation voltage of 800V and a maximum operational voltage of 500V DC. The maximum power loss is 15.4W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated insulation voltage is 800 V.
The maximum rated operational voltage is 500 V DC.
The current rating is 60A.
The breaking capacity at 480 V is 35 kA.
It has an electrical endurance of 8,000 cycles at 380/415 V.
It mounts on a DIN rail.
Yes, it is HACR type.