| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This Siemens 3VA5112-6ED16-0AA0 is a 1-pole molded-case circuit breaker from the 3VA5 UL frame series. It is designed for system protection and features a breaking capacity class H, with a maximum short-circuit current of 50kA at 277V.
The circuit breaker has an operational current rating of 125A at 40°C, with derated values at higher temperatures. It utilizes a TM210 overcurrent release with LI protection function and fixed overload (Ir) and short-circuit (Ii) settings. The rated operational voltage at AC is 415V, and the insulation voltage is 500V.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It is suitable for DIN rail mounting and has a degree of protection IP40. The connection is designed for aluminum lugs.
Key electrical specifications include a maximum power loss of 10.03W. The breaker is UL489 listed and meets HACR Type requirements. It is designed for line protection applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 125A at 40°C.
The breaking capacity is 50kA at 277V according to UL 489, and 55kA at 240V according to IEC 60947.
The rated operational voltage at AC is 415V.
It uses a TM210 overcurrent release with LI protection function.
It is designed for DIN rail mounting.