| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Voltage | |
| Voltage Rating |
This Siemens 3VA5112-6ED16-1AA0 is a 1-pole molded-case circuit breaker designed for system protection. It operates at a rated voltage of 415V AC and has a current rating of 125A at 40°C.
The circuit breaker features a breaking capacity of 50kA at 277V and 100kA at 120V, with overload protection set at Ir=125A and fixed short-circuit protection at Ii=10 x In. The overcurrent release type is TM210 with LI protection function.
With a mechanical service life of typically 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V and 480V, this breaker is built for durability. It is HACR Type approved and mounts on a DIN rail.
Additional specifications include a maximum power loss of 10.03W and a net weight of 0.404 kg. Compliance includes RoHS3, MSL 1, and REACH Unaffected.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage is 415 V AC.
The operational current is 125 A at 40 °C.
This circuit breaker has 1 pole.
The breaking capacity is 50 kA at 277 V.
The overload protection is set at Ir=125A.
The typical mechanical service life is 20,000 switching cycles.
Yes, it is HACR Type approved.