This Siemens 3VA5 molded-case circuit breaker, part number 3VA5112-4ED56-0AA0, is designed for system protection applications. It features a 1-pole configuration and a rated operational current of 125A at 40°C, with derated values at higher temperatures.
The breaker provides a breaking capacity of 25kA at 277V according to UL 489 standards and 5kA at 415V according to IEC 60947. It operates at a rated voltage of 415V AC and has a maximum DC operational voltage of 125V. The overcurrent release is of type TM210 with LI protection function.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V AC, this circuit breaker is built for durability. It is suitable for HACR Type applications and mounts via DIN rail.
Key electrical specifications include an insulation voltage of 500V and a maximum power loss of 10.03W. The breaker is marked according to UL 489 and carries CCC, CE, and VDE approvals.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 125A at 40°C, derating to 109A at 70°C.
It has a breaking capacity of 25kA at 277V (UL 489) and 5kA at 415V (IEC 60947).
The rated operating voltage at AC is 415V, and the maximum rated operational voltage with DC is 125V.
This is a 1-pole circuit breaker.
It is designed for DIN Rail mounting.