The Weidmüller HB Series 2823230000 is an AC/DC UL 489 branch circuit breaker designed for reliable protection. This ultra-compact, 13 mm wide module utilizes hydraulic-magnetic technology for consistent performance independent of ambient temperature.
Key electrical specifications include a 16A current rating, 240VAC/80VDC voltage rating, and a 2-pole configuration. It supports various time delay curves including instantaneous, short, medium, and long delays. The breaker is suitable for electrical isolation and features ON/OFF indication.
Designed for convenience, the 2823230000 features DIN rail mounting and box-type main terminals compatible with wire sizes from 0.75 mm² to 16 mm². It operates within an ambient temperature range of -40°C to +85°C and meets flammability and toxicity standards.
Applications for this circuit breaker include AC branch circuit protection, telecom/datacom equipment, lighting control, UPS systems, alternative energy, mobile power generation, railway signaling, residential, and industrial equipment.
Maximum operating voltage is 240 Vac or 80 Vdc.
-40°C to +85°C.
DIN rail mounting.
IEC: 6 kA at 240 Vac / 415 Vac. UL: 10 kA at 120/240 Vac / 80 Vdc.
Instantaneous, short, medium, and long.
IEC: 0.75 mm² to 16 mm². UL: 18-6 AWG.
2 poles.