| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Product Type | |
| Voltage Rating | |
| Weight |
The Weidmüller 2822270000 is a 2-pole magnetic (hydraulic delay) circuit breaker designed for overcurrent protection in industrial and commercial applications. It is rated for a nominal current of 16A, with a minimum current rating of 0.5A and a maximum of 32A. The breaker is UL 489 listed for 240Vac/80VDC and complies with IEC/EN 60947-2 for 240Vac and 415Vac operation. It features a lever actuator and mounts on standard DIN rail. The hydraulic-magnetic mechanism provides precise time delay curves including instantaneous, short, medium, and long delays, allowing selective coordination. The operating temperature range is -40°C to +85°C, and it has an endurance of 10,000 operations per IEC 60947-2. Dielectric strength is 2000 Vac, and rated impulse withstand voltage is 4 kV. The breaker weighs 110 g per pole and meets shock (10G) and vibration (5G) resistance standards. Flammability class I3 and toxicity class F1 ensure environmental safety. Approvals include CCC, CE, UL489, VDE, and IEC/EN 60947-2.
UL 489 rated 240Vac/80VDC; IEC/EN 60947-2 rated 240Vac and 415Vac.
-40°C to +85°C.
DIN rail mount.
Instantaneous, Short, Medium, Long.
CCC, CE, UL489, VDE, IEC/EN 60947-2.
Nominal 16A, with a range from 0.5A to 32A.
2000 Vac for one minute per IEC 60947-2.