| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Product Type | |
| SVHC Present | |
| Voltage Rating | |
| Weight |
The Weidmüller HB Series 2822250000 is a miniature circuit breaker designed for AC/DC branch circuit protection. It features ultra-compact dimensions, measuring only 13 mm wide per pole, and utilizes hydraulic-magnetic technology for reliable operation. This breaker is suitable for electrical isolation and provides ON and OFF indication.
Key electrical specifications include a 2-pole configuration, a current rating of 12A, and a voltage rating of 240V AC / 80V DC. It supports a wide range of operating voltages and current ratings from 0.5A to 32A, with various time delay curves available including instantaneous, short, medium, and long.
The circuit breaker is designed for DIN rail mounting and has an endurance rating of 10,000 operations. Environmental specifications include an operating temperature range of -40°C to +85°C, with certifications such as UL 489 and IEC/EN 60947-2.
Applications for this circuit breaker include AC branch circuit protection, telecom/datacom equipment, lighting control, UPS equipment, alternative energy, mobile power generation, railway signaling, residential, and industrial equipment.
It is rated for 240VAC/80VDC under UL 489 and 240/415Vac under IEC/EN 60947-2.
The continuous current rating is 12A, with an overall range of 0.5A to 32A depending on configuration.
It is a 2-pole circuit breaker.
It is a magnetic (hydraulic delay) circuit breaker.
It operates from -40°C to +85°C.
It is listed to UL 489 and complies with IEC/EN 60947-2, and has CCC, CE, and VDE approvals.
It mounts on DIN rail.