| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
The E-T-A 1658-G41-02-P10-D04-055845-8A is a single-pole thermal circuit breaker designed for overcurrent protection. It is rated for 8A continuous current at both 240VAC and 28VDC, making it suitable for a variety of AC and DC applications. The breaker features a push-to-reset actuator and panel mount installation, providing easy manual reset after a fault condition.
Electrical characteristics include a typical voltage drop of ≤250mV across all current ratings from 5A to 30A, ensuring minimal power loss. The interrupting capacity is 2,000A at 240VAC and 2,000A at 28VDC (2,500A at 32VDC), offering robust fault current interruption. The breaker meets UL 1077 and EN 60934 standards for supplementary protectors.
The operating temperature range is -20°C to +60°C, with a maximum ambient temperature of +40°C for currents ≤7A. The operating area is rated IP40 for protection against solid objects, while the terminal area is IP00. Dielectric strength is 3,000VAC, and insulation resistance exceeds 100MΩ at 500VDC. Typical life is 1,000 operations at 2x rated current under inductive or resistive loads.
240VAC and 28VDC.
8A.
-20°C to +60°C.
Thermal.
2,000A at 240VAC and 2,000A at 28VDC (2,500A at 32VDC).
Push to Reset.
Panel Mount.