| Category | |
| Manufacturer Name | |
| Accessory Type | |
| For Use With | |
| Frequency | |
| Input Connector |
The Bel Power Solutions YSD.00162 is an AC Power Distribution Unit (PDU) designed for use in IT Racks, specifically following the Open Rack specification and working with the OCP V2 Open Rack system. This unit is installed in an IT chassis and distributes AC voltage to V2 Power Shelves, which then provide DC power to the IT devices.
Key electrical specifications include a nominal AC input voltage of 277/480 VAC and a nominal continuous input current of 20 Arms per phase at 45°C ambient temperature. The PDU incorporates surge protection with 2 kV differential mode and 4 kV common mode ratings. It features an L22-20P input connector.
This PDU is compatible with the Open Compute Project Specification and is built with a robust mechanical design. It is suitable for applications requiring reliable AC power distribution within Open Rack environments. The unit is ROHS3 Compliant and has a Moisture Sensitivity Level (MSL) of 1.
The AC input voltage is 277/480 VAC.
The nominal continuous input current is 20 Arms per phase at 45°C ambient temperature.
It uses an L22-20P input connector.
The surge protection ratings are 2 kV for differential mode and 4 kV for common mode.
Yes, the YSD.00162 is ROHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1.