| Category | |
| Manufacturer Name | |
| Applications | |
| Approval Agency | |
| Current | |
| Efficiency | |
| Features | |
| Height | |
| Input Frequency | |
| Input Voltage | |
| Length | |
| Mounting Type | |
| Number of Outputs | |
| Operating Temperature | |
| Output Voltage | |
| Overload Protection | |
| Power (Watts) | |
| Type | |
| Voltage | |
| Width |
The Traco Power TMT 50112C is a 50 Watt AC/DC power module designed for industrial, ITE (Commercial), and Medical applications. It provides a single 12VDC output with a maximum current of 4.2A.
This fully encapsulated power module features a universal input voltage range of 85-264 VAC and operates at 50/60 Hz. It boasts an efficiency of 83% and includes protection class II compliance. The TMT 50112C is approved to IEC/UL 60950-1 safety standards and is UL 508 listed for chassis mount versions. It also meets EMI standards according to EN 55022 Class B and FCC Level B.
The unit is designed for chassis mounting and utilizes screw terminals for easy installation. Its compact dimensions are 110.0mm x 64.0mm x 33.5mm. The operating temperature range is -25°C to 50°C with derating. The series is also approved to the medical standard IEC60601-1 ed.3.0.
Key electrical specifications include a nominal output voltage of 12VDC, a maximum output current of 4.2A, and a maximum output power of 50W. Voltage regulation is 50 mV max. for load variation, and ripple and noise are 150 mVpk-pk max. Overload protection is provided by current limiting.
The Traco Power TMT 50112C provides a nominal output voltage of 12 VDC with a maximum output current of 4.2 A.
The TMT 50112C power module accepts a universal input voltage range of 85-264 VAC.
The TMT 50112C has a maximum operating temperature range of -25°C to 50°C with derating.
The TMT 50112C is approved to the IEC/UL 60950-1 safety standard and is UL 508 listed for chassis mount versions.
The TMT 50112C is designed for chassis mounting and features a screw terminal block.
Yes, the TMT 50112C is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) for the TMT 50112C is 1 Unlimited.