The Schurter TA45-ABFRF080C0-AZM11 is a 2-pole thermal circuit breaker from the TA45 series, suitable for various industrial applications. It features a rocker actuation type and a panel mount, snap-in design for easy installation.
This circuit breaker operates with a rated AC voltage of 240 VAC and a rated DC voltage of 60 VDC. The AC current rating ranges from 0.05A to 20A, with this specific model rated at 8A. It provides a conditional short circuit capacity of 1 kA at 240 VAC and a short circuit capacity (Icn) of 300A at 240 VAC for currents 3A and above.
Key technical specifications include a dielectric strength of 4 kVAC, insulation resistance greater than 100 MΩ at 500 VDC, and a mechanical lifetime of 50,000 switching cycles. The operating temperature range is -10°C to 55°C, with a storage temperature range also from -10°C to 55°C. It meets IP40 degree of protection on the front side.
Approvals include CSA C22.2 No 235, IEC60934, GB17701, and UL1077, indicating compliance with relevant safety standards for equipment protection.
The rated voltage is 240 VAC and 60 VDC.
The current rating is 8A.
This circuit breaker has 2 poles.
It uses a rocker actuation type.
The allowable operation temperature is -10 °C to 55 °C.