The Mean Well USA NFM-05-15 is a 5W on-board type AC/DC converter designed for medical and general electronic applications. It provides a single 15V output with a rated current of 330mA and operates within a universal input voltage range of 85-264VAC or 120-370VDC.
This converter features Class II isolation, making it suitable for non-patient contact medical equipment. It includes standard protections such as short circuit, overload, over voltage, and over temperature. The low no-load power consumption of less than 0.5W complies with 'green mode' requirements.
With dimensions of 58.0mm x 45.0mm x 19.1mm, it is designed for through-hole mounting. The operating temperature range is -20°C to +70°C with derating. Compliance includes UL60601-1 and TUV EN60601-1 medical standards, along with EMC compliance to EN55011 Class B and EN55022 Class B.
Key electrical specifications include an efficiency of 74%, a ripple and noise voltage of 150mV, and an isolation resistance of 100M Ohms at 500VDC. The MTBF is rated at a minimum of 738.7Khrs.
85~264 VAC or 120~370 VDC.
Module, open frame.
-20°C to +70°C with derating.
UL60601-1, TUV EN60601-1, CB, CE, cURus, EAC, TUV.
15V DC at 330mA (0.33A), 5W.
Overload (hiccup mode, auto recovery), over voltage (shut off), over temperature (auto recovery).
74%.