HPT5K0TS100 AC/DC converter from XP Power delivering 5000W at 100V DC output. Accepts 3-phase input from 180-528VAC.
Mfr Part #:

HPT5K0TS100

Mfr Name: XP Power
XP Power
AC/DC converter from XP Power delivering 5000W at 100V DC output. Accepts 3-phase input from 180-528VAC.
Stock on Request

HPT5K0TS100 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Applications
Approval Agency
Current
Efficiency
Features
Height
Length
Mounting Type
Number of Outputs
Operating Temperature
Power (Watts)
SVHC Present
Standard Number
Type
Voltage
Width

HPT5K0TS100 Description

Short technical summary and product information.

The HPT5K0TS100 is a 5000W AC/DC converter from XP Power, designed for high-power industrial applications. It provides a single 100V DC output and accepts a three-phase AC input ranging from 180 to 528 VAC at 47-63 Hz.

 

Key electrical specifications include a power factor of 0.96, complying with EN61000-3-2 Class A, and an input current of 10 A per phase at 342 VAC (5kW) or 11 A per phase at 180 VAC (2.5kW). Inrush current is limited to 60 A per phase at 528 VAC. Earth leakage current is 1.0 mA maximum under normal conditions and 3.3 mA under single fault condition, both at 528 VAC/60Hz.

 

Input protection is provided by F16A / 500V fuses fitted in each phase. The converter is suitable for use in server, telecom, test and measurement, and industrial power systems where high efficiency and reliable performance are required.

HPT5K0TS100 Quick Information

Product Type: AC/DC Converter
Series: HPT5K0
Canonical Name: AC/DC Converter 5000W, 100V Output, 3-Phase Input
Subcategory: High Power AC/DC Converter

HPT5K0TS100 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

HPT5K0TS100 Features

  • 5000W single output AC/DC converter.
  • Input voltage range 180-528 VAC.
  • Power factor correction to 0.96.
  • Input protection with F16A fuse per phase.
  • Earth leakage current less than 1.0 mA.

HPT5K0TS100 Applications

  • Ideal for high-power industrial power supplies.
  • Used in three-phase AC input systems.
  • Suitable for server and telecom infrastructure.
  • Applicable in test and measurement equipment.

HPT5K0TS100 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the input voltage range of the HPT5K0TS100?

The input voltage range is 180 to 528 VAC (three-phase).

What is the input frequency range?

The input frequency range is 47 to 63 Hz.

What is the power factor of this converter?

The power factor is 0.96, complying with EN61000-3-2 Class A.

What is the input current rating?

Typical input current is 10 A per phase at 342 VAC (5kW) and 11 A per phase at 180 VAC (2.5kW).

What is the inrush current?

Inrush current is 60 A per phase at 528 VAC (5kW).

What is the earth leakage current?

Earth leakage current is 1.0 mA maximum under normal conditions and 3.3 mA under single fault condition, both at 528 VAC/60Hz.

What input protection is provided?

Input protection is provided by F16A / 500V fuses fitted in each phase.