| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Prop 65 | |
| Standards | |
| Voltage Rating | |
| Width |
The Schneider Electric GP2E05 is a manual motor controller designed for motor applications. It belongs to the Easy TeSys GP2E product range and utilizes a thermal-magnetic trip unit technology.
This 3-pole controller operates on AC networks with a frequency of 50/60 Hz. It has a line rated current of 1A and a thermal protection adjustment range of 0.63 to 1A, with a magnetic tripping current of 13A. The rated operational voltage (Ue) and rated insulation voltage (Ui) are both 690V AC.
Designed for reliability, the GP2E05 offers a breaking capacity (Icu) of 100 kA across various voltages up to 690V AC. It also provides a rated service short-circuit breaking capacity (Ics) of 100% at these voltages. The controller is suitable for isolation and features phase failure sensitivity.
Installation is facilitated by its 35 mm symmetrical DIN rail clipping mechanism, though panel mounting with an adaptor plate is also possible. The device has a mechanical and electrical durability of 100,000 cycles. Its dimensions are 89 mm in height, 45 mm in width, and 78.5 mm in depth, with a weight of 0.26 kg.
690 V AC.
-20 to 60 °C.
100 kA Icu at all voltages from 230 V to 690 V AC.
3 poles.
EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, cUL.
1 A.
Yes, it is suitable for isolation per IEC 60947-1.