| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Voltage | |
| Voltage Rating |
The Altech Corporation GFL2C080302 is a 2-pole Branch Circuit Breaker with Equipment Ground Fault Protection (RCBO) from the GFL Series. It is rated for 8A at 240V AC and features a residual operating current sensitivity of 30mA. This breaker provides protection against short circuits, overloads, AC ground faults, and pulsating DC ground faults.
Designed for reliable operation, the GFL2C080302 has a rated short circuit capacity of 10kA and supports overload tripping curves B, C, and D. It is suitable for use with cable sizes ranging from 14 to 3 AWG and requires a tightening torque of 17.5 lb-in (2.0 Nm). The electrical life is rated for 6000 switching operations, and the mechanical life is rated for 10000 switching operations.
This circuit breaker is designed for DIN rail mounting, making installation convenient in various electrical enclosures. It operates within an ambient temperature range of -25°C to 40°C. The GFL2C080302 is UL489 listed, ensuring compliance with safety standards.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated current is 8A.
The rated voltage is 240V AC.
The rated residual operating current is 30mA.
It has 2 poles.
The rated short circuit capacity is 10kA.
The ambient temperature range is -25°C to 40°C.
It supports DIN rail mounting.