| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
The Schneider Electric TeSys GB2 GB2DB14 is a 2-pole thermal magnetic circuit breaker suitable for control applications. It operates on AC/DC networks with a rated operational voltage of 415V AC and 48V DC.
This circuit breaker features an 8A line rated current and a magnetic tripping current of 108A. Its breaking capacity varies by voltage, with 3kA at 110V AC and 1.5kA at higher AC voltages and DC voltages. The device utilizes a thermal-magnetic trip unit technology and has a utilization category of Category A.
Designed for easy mounting, it can be attached via clips to a plate or rail in vertical or horizontal positions. The GB2DB14 has a toggle control type and offers mechanical and electrical durability of 8000 cycles each. Its dimensions are 74mm in height, 30mm in width, and 70mm in depth, with a net weight of 0.115 kg.
The operating temperature range is -20°C to 60°C, and it has an IP20 degree of protection. The circuit breaker complies with EN/IEC 60947-1 and EN/IEC 60947-2 standards.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The line rated current is 8A.
The rated operational voltage is 415V AC and 48V DC.
The breaking capacity is 3kA at 110V AC and 1.5kA at 230/240V AC, 400/415V AC, and 24V DC.
It uses a thermal-magnetic trip unit.
The operating temperature range is -20°C to 60°C.
It is designed for DIN rail mounting and can be attached via clips to a plate or rail.