| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
The Schneider Electric TeSys GB2 GB2DB12 is a thermal magnetic circuit protector designed for control applications. This 2-pole device has a line-rated current of 6A and supports both AC and DC networks.
Key electrical specifications include a rated operational voltage of 415V AC at 50/60 Hz and 48V DC. The breaking capacity (Icu) is 3kA at 110V AC and 1.5kA at 230/240V AC, 400/415V AC, and 24V DC. For DC applications, it provides 1kA at 48V DC. The rated service short-circuit breaking capacity (Ics) is 75% across various AC voltage ranges.
Featuring a thermal-magnetic trip unit technology, it has a magnetic tripping current of 83A. The circuit breaker is designed for mounting on a DIN rail or plate using clips. It has a mechanical and electrical durability of 8000 cycles.
Environmental specifications include an operating temperature range of -20°C to 60°C and a fire resistance of 960°C. The device has an IP20 degree of protection and an operating altitude of up to 3000 meters.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The line-rated current is 6A.
It is rated for 415V AC at 50/60 Hz and 48V DC.
The breaking capacity (Icu) is 3kA at 110V AC, 1.5kA at 230/240V AC, 400/415V AC, and 24V DC, and 1kA at 48V DC.
The operating temperature range is -20°C to 60°C.