The Schneider Electric GB2DB10 is a TeSys GB2 series thermal magnetic circuit breaker. It features 2 poles and is designed for control applications. The device has a line rated current of 5A and a rated operational voltage of 415V AC at 50/60 Hz, and 48V DC.
Key electrical characteristics include a breaking capacity (Icu) of 3 kA at 110V AC and 2 kA at 230/240V AC and 400/415V AC. The magnetic tripping current is 66A. The trip unit technology is thermal-magnetic.
This circuit breaker is designed for DIN rail mounting and features a toggle control type. It has a mechanical and electrical durability of 8000 cycles. The operating ambient air temperature range is -20 to 60 °C.
Standards include EN/IEC 60947-1 and EN/IEC 60947-2. The IP degree of protection is IP20.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The line rated current is 5A.
The rated operational voltage is 415V AC at 50/60 Hz and 48V DC.
It has 2 poles.
It supports DIN rail mounting.
The ambient air temperature for operation is -20 to 60 °C.