The Schneider Electric TeSys GB2 GB2CD06 is a thermal magnetic circuit breaker designed for control applications. It offers a 1P+N pole configuration and a line rated current of 1A. The device operates on AC/DC networks with a rated operational voltage of up to 250V AC and 48V DC, and is compliant with standards such as IEC 60947-2.
This circuit breaker features a thermal-magnetic trip unit technology with a magnetic tripping current of 14A. It is designed for DIN rail mounting and has a toggle actuator type. The device offers a breaking capacity of 50 kA at 110V AC and 230/240V AC, and 1.5 kA at 24V DC.
With a mechanical and electrical durability of 8000 cycles, the GB2CD06 is built for reliability. It has an IP20 degree of protection and an operating temperature range of -20°C to 60°C. The compact dimensions of 74mm height, 15mm width, and 67mm depth make it suitable for various control panel installations.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The line rated current is 1A.
It has 1P + N poles.
The rated operational voltage is 250V AC, 277V AC, and 48V DC.
The ambient air temperature for operation is -20 to 60 °C.
The RoHS status is RoHS3 Compliant.
The MSL is 1 Unlimited.