| Category | |
| Manufacturer Name | |
| Accessory Type | |
| Frequency | |
| Rated Current |
The Enerdoor FINHRM5C.110.M-60 is a passive harmonic filter used to mitigate harmonic distortion in AC power systems, particularly in variable frequency drive applications. It is rated for a nominal voltage of 0-480 VAC (HV version up to 690 VAC) and a frequency range of 50-60 Hz. The rated current is 110 A, with a range capability of 10-750 A for the product family.
The filter provides overload capabilities: 4x rated current during switch-on, 2x In for 10 seconds, and 1.5 In for 10 minutes. Dielectric strength is tested at 2400 Vdc phase-to-phase and 3200 Vdc phase-to-ground for 2 seconds. Power loss at 480 VAC is 775 W, and rated power is 64 kW at 480 VAC. The unit has an IP20 protection rating for currents up to 210 A and IP00 for currents above 210 A. Climatic class is -40 to +85°C, with an MTBF of 250,000 hours at 40°C. The filter is designed for industrial environments and is suitable for use with AC drives and other harmonic-generating loads.
The nominal voltage range is 0-480 VAC, with an HV version supporting up to 690 VAC.
The operating temperature range is -40 to +85°C.
The rated current is 110 A, with a family range of 10-750 A.
It can handle 4x rated current during switch-on, 2x In for 10 seconds, and 1.5 In for 10 minutes.
IP20 for currents up to 210 A, and IP00 for currents above 210 A.
The power loss is 775 W at 480 VAC.
The MTBF is 250,000 hours at 40°C.