FC-R1 The AUTOMATION FC-R1 is a loop-powered, non-isolated signal conditioner designed for RTD inputs. It converts RTD signals into a linearized 4-20 mA current loop output.
Mfr Part #:

FC-R1

Available from 1 distributors
Mfr Name: Automation
Automation
The AUTOMATION FC-R1 is a loop-powered, non-isolated signal conditioner designed for RTD inputs. It converts RTD signals into a linearized 4-20 mA current loop output.
✓ Total Stock: 2 pcs
$ Price Range: $4.95

FC-R1 Available from 1 distributor

✓ Authorised
✓ Non-Authorised
Distributor Stock Pricing MOQ PKG Lead Time Date Code On Order Quantity On Order Delivery
Non-Authorised Inventory information
2 pcs
2 pcs On Request 1 On Request On Request On Request On Request On Request

FC-R1 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Input Type
Isolation
Mounting Type
Output Type
Stability

FC-R1 Description

Short technical summary and product information.

The FC-R1 from AUTOMATION is a versatile DIN rail mount signal conditioner specifically designed for Resistive Temperature Detector (RTD) inputs. This loop-powered device converts RTD signals into a linearized 4-20 mA current loop, making it suitable for interfacing RTD sensors with PLC analog input modules.

 

The FC-R1 offers user-selectable input types, including CU10 (10 Ohm Copper), PT100 (100 Ohm Platinum), and PT1000 (1000 Ohm Platinum) RTDs. It also provides user adjustments for OFFSET (zero) and SPAN (full scale) of the output signal, with ranges of 0-25% for offset and 80-102% for span. The unit is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-hazardous locations.

 

Key specifications include a maximum loop supply of 30VDC and various input ranges depending on the RTD type selected. For example, the PT100 input range is -200°C to 850°C (-328°F to 1562°F). The signal conditioner features adjustable OFFSET and SPAN, and a linearized 4-20mA output.

 

Designed for industrial applications, the FC-R1 facilitates accurate temperature measurements by conditioning signals from RTD sensors. Its DIN rail mounting ensures easy integration into control panels. Shielded RTDs are recommended for use with this conditioner to minimize noise.

FC-R1 Quick Information

Product Type: Signal Conditioner
Canonical Name: FC-R1 Loop Powered Signal Conditioner
Subcategory: RTD Input

FC-R1 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

FC-R1 Estimated Pricing

Qty Low High
1+ $4.95 $4.95

Estimated market price range - modelled values for guidance only, not live distributor offers.

FC-R1 Features

  • Converts RTD signals to 4-20mA current loop.
  • User-selectable CU10, PT100, PT1000 RTD inputs.
  • Adjustable offset and span controls.
  • DIN rail mountable for easy installation.
  • Suitable for Class I, Division 2 hazardous locations.

FC-R1 Applications

  • Industrial temperature monitoring.
  • PLC analog input signal conditioning.
  • Process control systems.
  • Remote temperature sensing.

FC-R1 FAQs

6 frequently asked questions generated from this part’s specifications.
What types of RTD inputs does the FC-R1 support?

The FC-R1 supports CU10 (10 Ohm Copper), PT100 (100 Ohm Platinum), and PT1000 (1000 Ohm Platinum) RTD inputs.

What is the output signal of the FC-R1?

The FC-R1 outputs a linearized 4-20 mA current loop.

What is the input temperature range for a PT100 sensor with the FC-R1?

The input temperature range for a PT100 sensor is -200°C to 850°C (-328°F to 1562°F).

What is the maximum loop supply voltage for the FC-R1?

The maximum loop supply voltage for the FC-R1 is 30VDC.

How is the FC-R1 signal conditioner mounted?

The FC-R1 is designed for DIN rail mounting.

Is the FC-R1 suitable for hazardous locations?

Yes, the FC-R1 is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-hazardous locations.