The Tri-Mag DG200-JEU is a 200 Watt open-frame AC/DC power supply designed for ITE (Commercial) applications. It operates with a universal input voltage range of 90 VAC to 264 VAC and provides a single 48V output.
Key electrical specifications include a typical efficiency of 90%, active Power Factor Correction (PFC), and a low no-load input power of less than 0.5W. The unit offers robust protection features such as overvoltage, overload, and short circuit protection with auto-recovery. It operates within a temperature range of -20°C to 65°C and supports both free air convection cooling for 200W and forced air cooling for up to 300W.
Designed for reliability and safety, the DG200-JEU meets UL/CSA/EN 60950-1 (ITE) and ANSI/AMMI/CSA/EN 60601-1 (Medical) standards, with CE Mark and CB report. It also complies with EMC standards including EN55022 Class B and EN 61000-3-2 Class D. The power supply is built with 4000 VAC isolation from input to output and is approved for 2xMOPP applications.
This open-frame converter has a compact size of 76.2 x 127.0 x 36.1 mm (3.0 x 5.0 x 1.42 in) and is suitable for chassis mounting. It comes with a 10-year manufacturer's warranty.
The DG200-JEU accepts a universal input of 90-264 VAC at 47-63 Hz.
The DG200-JEU provides a nominal 48V output.
The DG200-JEU delivers 200W in free-air convection and 300W with 18 CFM forced air.
The DG200-JEU is approved to UL/CSA/EN 60950-1 2nd edition (ITE) and ANSI/AAMI/CSA/EN 60601-1 3rd edition (Medical), and carries CE Mark and CB report.
The DG200-JEU provides 4000 VAC input-to-output, 1500 VAC input-to-ground, and 1500 VDC output-to-ground isolation, with 2xMOPP approval.
The DG200-JEU operates from -20°C to 65°C with derating of 3.33% per °C above 50°C.
The DG200-JEU includes overvoltage protection with latch-off, and overload and short-circuit protection with auto recovery.