The Advanced Energy CoolX®1000 series, including the CX10S-B0ABDD-P-A-DK00000, is a fanless 1000W modular power supply designed for applications requiring quiet operation and high reliability. Packaged in a compact U-channel design measuring 259.5 mm x 164 mm x 40.6 mm, it provides 1000W of power without fan or base plate cooling, eliminating acoustic noise and vibrations.
This power supply features 5 outputs, including a nominal 12V output capable of delivering 4.17A, with a total power output of 865W. It boasts a high efficiency of 93% and supports universal input. The CX10S series is designed for ITE (Commercial) and Medical applications, complying with standards such as IEC60601-1, IEC60950-1, and IEC62368-1.
Flexibility is enhanced with analog and digital management via PMBus™ for monitoring and control. It supports field configuration for plug-and-play power and allows for series and parallel output configurations for higher voltages or currents. The unit is safety approved for operation up to 5000m altitude and operates within a wide temperature range of -40°C to 85°C.
Mounting is facilitated via a chassis mount design, with options for base/side and DIN-Rail mounting. Key reliability features include an MTBF of over 2,900,000 hours and high-input surge protection up to 4 kV line to PE.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The CX10S series provides a total power output of 1000 W.
The dimensions are 259.5 mm x 164 mm x 40.6 mm.
The operating temperature range is -40°C to 85°C.
Yes, the RoHS Status is RoHS3 Compliant.
The MTBF is greater than 2,900,000 hours.
It meets IEC60601-1 3rd edition, IEC60601-1-2 4th edition (EMC), IEC60950, and IEC62368-1.