This OptiFuse CBW68-HF-70A-5P is a thermal circuit breaker with a 70A current rating, suitable for 250VAC or 50VDC systems. It offers a push-to-reset actuator for convenient operation and a panel mount design for easy integration into equipment.
The circuit breaker is built for occasional overcurrent protection, featuring a dielectric strength of 1500 VAC for one minute and an insulation resistance greater than 500MΩ. Its contact endurance is rated for over 500 cycles at 125 VAC with 150% of the rated current. The reset time is less than 60 seconds.
Calibration specifications indicate that the device will hold at 100% of rated current, trip within 1 hour at 150% of rated current, and trip within 8.5-45.0 seconds at 200% of rated current. It is designed for standard profile applications and is intended for occasional overcurrent protection scenarios.
Warning: Operation beyond specified maximum ratings or improper use may result in damage, electrical arcing, or flame. Avoid contact with chemical solvents, as prolonged contact may damage device performance.
The current rating is 70A.
It can handle 250 VAC or 50 VDC.
It is a thermal circuit breaker.
It features a push-to-reset actuator.
It is designed for panel mounting.
The interrupt capacity is 1000A at 125 VAC and 200A at 250 VAC.
The dielectric strength is 1500 VAC for 1 minute.