| Distributor | Stock | Pricing | MOQ | PKG | Lead Time | Date Code | On Order Quantity | On Order Delivery | |
|---|---|---|---|---|---|---|---|---|---|
|
7 pcs
|
7 pcs | On Request | 1 | On Request | On Request | On Request | On Request | On Request |
| Category | |
| Manufacturer Name | |
| Applications | |
| Approval Agency | |
| Configuration | |
| Current | |
| Filter Type | |
| Frequency | |
| Inductance | |
| Lead Style | |
| Mounting Type | |
| Tape & Reel | |
| Termination Style | |
| Voltage |
The B84143V0025R227 from TDK Corporation is a single stage three-phase (Delta) line filter designed for sine-wave output filtering in converter applications. It is rated for a nominal voltage of 520 V AC and a continuous current of 25 A at 40°C. The filter provides an inductance of 2.5 mH and is capable of handling overloads of 1.5 times the rated current for one minute per hour.
Test voltages are specified at 1500 V DC between lines and 2500 V DC between lines and case. The filter is chassis mounted with terminal block terminations and offers an IP20 degree of protection. It is cURus approved with an insulation system class F (155°C).
Typical applications include frequency converters for motor drives such as elevators, pumps, traction systems, and HVAC equipment. The design reduces motor noise, eddy current losses, and dv/dt, making it suitable for long motor cable runs. Natural cooling is employed, and wiring between the inverter and filter must be kept under 10 meters.
| Qty | Low | High |
|---|---|---|
| 1+ | $554.98 | $554.98 |
| 10+ | $535.84 | $535.84 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated voltage is 520 V AC (300/520 V AC per datasheet).
The rated current is 25 A at 40°C.
Chassis mount with terminal block terminations.
The inductance is 2.5 mH.
It is cURus approved.
The test voltage between lines and case is 2500 V DC.
It can handle 1.5 times the rated current for 1 minute per hour.