5SJ4211-7HG41 The Siemens 5SJ4211-7HG41 is a 2-pole miniature circuit breaker with a 5A operational current and a C-trip characteristic. It offers a 14kA short circuit breaking capacity according to UL 1077 and CSA C22.2 No.235.
Mfr Part #:

5SJ4211-7HG41

Mfr Name: Siemens
Siemens
The Siemens 5SJ4211-7HG41 is a 2-pole miniature circuit breaker with a 5A operational current and a C-trip characteristic. It offers a 14kA short circuit breaking capacity according to UL 1077 and CSA C22.2 No.235.
Stock on Request

5SJ4211-7HG41 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Current Rating
Current Rating (Amps)
Depth
Halogen Free
Height
Illumination
Mounting Type
Number of Poles
Supply Voltage
Voltage Rating
Width

5SJ4211-7HG41 Description

Short technical summary and product information.

This Siemens 5SJ4 miniature circuit breaker is designed for reliable protection in industrial and mechanical engineering applications. It features a 2-pole configuration with a 5A rated operational current and a C-trip characteristic, suitable for protecting circuits against overloads and short circuits.

 

The breaker operates at a rated supply voltage of 400V AC and has an AC operating voltage of up to 240V according to UL 489 and CSA C22.2 No. 5-02. It boasts a high switching capacity current of 10 kA according to EN 60898 and 15 kA according to IEC 60947-2, with a short circuit breaking capacity of 14 kA.

 

Constructed with halogen-free and silicon-free materials, this circuit breaker ensures environmental compliance. It features touch protection and combined terminals for ease of installation. The device is designed for DIN rail mounting and has dimensions of 110mm height, 36mm width, and 70mm depth, with an installation depth of 70mm. It supports conductor cross-sections from 0.75 mm² to 25 mm² with core end processing.

5SJ4211-7HG41 Quick Information

Product Type: Miniature Circuit Breaker
Series: 5SJ4
Canonical Name: Siemens 5SJ4 Miniature Circuit Breaker, 2-Pole, 5A, C-Trip
Subcategory: MCB

5SJ4211-7HG41 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

5SJ4211-7HG41 Features

  • 2-pole miniature circuit breaker.
  • 5A rated operational current.
  • C-trip characteristic.
  • 14kA short circuit breaking capacity.
  • UL 489 and CSA compliant.

5SJ4211-7HG41 Applications

  • Industrial power distribution.
  • Machine control circuits.
  • Protection against overloads.
  • Protection against short circuits.

5SJ4211-7HG41 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the tripping characteristic of this circuit breaker?

C-curve.

What are the operating voltage ratings?

Rated AC supply voltage 400V, insulation voltage 440V; max AC operating voltage 240V (UL/CSA). DC operation: max 60V single-channel, max 125V 2-channel.

What is the short-circuit breaking capacity?

10kA per EN 60898, 15kA per IEC 60947-2, and 14kA per UL 1077.

How is this circuit breaker mounted?

On standard DIN rail, in any mounting position.

What approvals does this circuit breaker have?

CCC, CE, CSA, EAC, UL, VDE.

How does ambient temperature affect the operational current rating?

The rated current is 5A at 30°C and 40°C, de-rating to 4.9A at 45°C, 4.8A at 50°C, 4.6A at 55°C, and 4.5A at 60°C.

What is the ingress protection rating?

IP20 generally, IP40 in the handle area with connected conductors.