The Schurter Inc. 4435.025 is a 2-pole thermal circuit breaker designed for equipment protection. It offers a rated current of 5A and a voltage rating of 240 VAC, with a DC rating of 60 VDC.
This circuit breaker features thermal tripping and a rocker actuation type, suitable for panel mounting. It has a mechanical lifetime of 50,000 switching cycles and an operating temperature range of -30°C to 60°C. The device also includes green illumination with a nominal voltage of 120V.
Key specifications include a conditional short circuit capacity of 2 kA at 240 VAC and an insulation resistance greater than 100 MΩ at 500 VDC. The degree of protection on the front side is IP40.
Applications for this circuit breaker include power tools, medical and laboratory equipment, industrial appliances, and commercial kitchen appliances.
It is rated for 240 VAC (IEC) / 277 VAC (UL/CSA) and 60 VDC.
The device is packaged in bulk and mounts on a panel.
The operating temperature range is -30°C to 60°C, with storage temperature from -40°C to 60°C.
It uses thermal tripping (thermal-magnetic available).
The dielectric strength is greater than 2.5 kV at 50 Hz and greater than 4 kV impulse (1.2/50 μs).
It is rated for 50,000 switching cycles under various load conditions.