The Schurter Inc. 4435.001 is a thermal circuit breaker with a 6A current rating and a voltage rating of 240V AC. It is designed for panel mounting and features a rocker actuator for operation. This 2-pole breaker offers a tripping type of Thermal-Magnetic, providing reliable protection.
Key electrical specifications include a rated voltage of 240 VAC (IEC) and 277 VAC (UL/CSA), with a DC rating of 60 VDC. The rated current range is from 0.05 to 20A. It has a conditional short circuit capacity of 2 kA at 240 VAC. The breaker is built to withstand demanding environments, with an operating temperature range of -30°C to 60°C and a mechanical lifetime of 50,000 switching cycles.
Applications for this circuit breaker include power tools, medical and laboratory equipment, industrial appliances, and equipment for construction. Its robust design and thermal-magnetic tripping mechanism make it suitable for various industrial and commercial uses.
The breaker is rated for 240 VAC (IEC), 277 VAC (UL/CSA), and 60 VDC operation.
Operating temperature range is -30°C to 60°C, storage temperature range is -40°C to 60°C.
The breaker provides 50,000 switching cycles under AC and DC load conditions, and 50,000 mechanical cycles.
It is designed for panel mounting with a rocker actuator type.
Front side protection is IP40 according to IEC 60529.
Yes, it is rated for 60 VDC operation.
Conditional short circuit capacity is 2 kA at 240 VAC.