| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Illumination Voltage (Nominal) | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Voltage Rating | |
| Weight |
The Schurter Inc. 4430.2618 is a 2-pole thermal circuit breaker designed for reliable overload protection. It offers a rated voltage of 240 VAC and 60 VDC, with a current rating range of 0.05 to 20 A AC. This breaker features a thermal tripping mechanism and rocker actuation for easy operation.
Key technical specifications include a dielectric strength of 4 kVAC, insulation resistance greater than 100 MΩ at 500 VDC, and mechanical lifetime of 50,000 switching cycles. The operating temperature range is -10 °C to 55 °C.
Designed for panel mounting, this circuit breaker has a degree of protection of IP40 on the front side, which can be increased to IP54 with a factory-mounted protection cover. It is suitable for various applications including power tools, industrial appliances, power supplies, and equipment for construction and cleaning.
Approvals include CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, and UL1077, ensuring compliance with international safety standards.
The rated voltage is 240 VAC and 60 VDC.
The rated current is 10 A, with an AC rated current range of 0.05 A to 20 A.
-10 °C to 55 °C.
Rocker actuation.
2 poles.
CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, and UL1077.