| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Voltage Rating | |
| Weight |
The Schurter Inc. 4430.2292 is a 2-pole thermal circuit breaker with a panel mount design and rocker actuation. It offers a rated voltage of 240 VAC and 60 VDC, with a current rating range of 0.05 to 20 A, and specifically 500mA for this model.
This circuit breaker provides thermal overload protection and features a positively trip-free release. It has a mechanical lifetime of 50,000 switching cycles and an overload capability of a minimum of 40 trips at 6 times the rated current for AC.
The device operates within an allowable temperature range of -10 °C to 55 °C and has a degree of protection of IP40 on the front side. Approvals include CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, and UL1077.
Applications for this type of circuit breaker include power tools, industrial appliances, power supplies, equipment for construction, and cleaning equipment.
Rated AC voltage: 240 VAC; Rated DC voltage: 60 VDC.
-10 °C to 55 °C.
Panel mount.
Thermal.
2 poles.
Rocker.
CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, UL1077.