| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Illumination Voltage (Nominal) | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Voltage Rating | |
| Weight |
This Schurter Inc. 4430.1064 is a thermal circuit breaker with a 2-pole configuration, suitable for panel mounting applications. It offers a current rating of 5A and can handle up to 240 VAC or 60 VDC.
The breaker utilizes thermal tripping and rocker actuation for reliable operation. It has a mechanical lifetime of 50,000 switching cycles and an overload capability of a minimum of 40 trips at 6 times the rated current for AC.
Designed for industrial environments, this circuit breaker operates within a temperature range of -10 °C to 55 °C. It meets various approval standards including CSA, EN, GB, IEC, and UL.
The breaker is rated for 240 VAC and 60 VDC.
The rated current is 5 A.
The allowable operating temperature is -10 to 55 °C.
The part is supplied in bulk packaging.
Conditional short circuit capacity is 1 kA at 240 VAC; short circuit capacity Icn is 300 A at 240 VAC for In ≥ 3 A.
The mechanical lifetime is 50,000 switching cycles.
It is approved under CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, and UL1077.