| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Rated Current | |
| Terminal Size | |
| Terminal Type | |
| Voltage Rating | |
| Weight |
The Schurter Inc. 4404.0007 is a thermal circuit breaker from the T9-611 series, designed for reliable circuit protection in various applications. This 1-pole breaker features a snap-in mounting type suitable for front-side installation into panels with material thickness from 0.8 to 2.0mm. It offers a rated current of 5A and can handle AC voltages up to 240V and DC voltages up to 48/32V.
With a degree of protection rated at IP40 for the front side, this circuit breaker is suitable for use in industrial appliances, power supplies, and HVAC systems. It is designed with a push-to-reset actuator and a cycling trip-free release mechanism, ensuring safe and convenient operation. The breaker meets various product standards including IEC 60934, UL 1077, CSA C22.2 No. 235, and GB 17701, and is suitable for applications compliant with IEC/UL 62368-1.
Key electrical specifications include a conditional short circuit capacity of 2 kA and an insulation resistance greater than 1000 MΩ at 500 VDC. The operating temperature range varies slightly with current rating, generally from -5°C to 60°C. Endurance specifications indicate a minimum of 50 switching cycles at 200% Ir and typical endurance of 2500 cycles for 3-8A and 6000 cycles for 10-16A at 150% Ir.
It is rated for 240 VAC and 48/32 VDC.
Panel mount with quick connect terminals (6.3 x 0.8 mm).
-5°C to 60°C.
Designed according to IEC 60934, UL 1077, CSA C22.2 No. 235, and GB 17701.
Conditional short circuit capacity is 2 kA at both 240 VAC (IEC and UL/CSA) and 48/32 VDC (UL/CSA).
Dielectric strength is 1500 VAC. Insulation resistance is greater than 1000 MΩ at 500 VDC.
For 3-8 A ratings typical endurance is 2500 switching cycles; for 10-16 A it is 6000 cycles. Minimum endurance is 50 cycles at 200% rated current.