The Schurter Inc. 4400.0495 is a thermal circuit breaker designed for equipment protection. This 1-pole breaker features a snap-in version with quick connect terminals (6.3 x 0.8 mm) and a push-to-reset actuation type.
Key electrical specifications include a rated AC voltage of 240 VAC and a rated DC voltage of 48 VDC. The rated current range is from 0.05 to 16 A, with a specific rating of 2.5A for this model. It offers a conditional short circuit capacity of 2 kA (AC 240V) and a short circuit capacity Icn of 8 x In (for In < 6.5 A) or 96 A (for In ≥ 6.5 A).
Environmental and mechanical features include a degree of protection of IP40, dielectric strength greater than 1.5 kV (50 Hz) and 2.5 kV (1.2/50 μs impulse), and insulation resistance greater than 100 MΩ at 500 VDC. The operating temperature range is -5 °C to 60 °C. Endurance is rated typically at 500 switching cycles and a minimum of 50 switching cycles for reset types. Overload testing per IEC standards requires a minimum of 40 trips at 6 x Ir, and per UL/CSA standards, a minimum of 50 trips at 1.5 x Ir.
This circuit breaker is suitable for applications such as power tools, household equipment, power supplies and chargers, and industrial appliances. It has approvals from CSA, EN, GB, IEC, and UL.
240VAC and 48VDC.
Panel mount.
-5°C to 60°C.
2.5A.
CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, UL1077.
Thermal.
IP40 on the front side.