4230-T130-K0DE-1A Thermal-magnetic circuit breaker rated at 1A with 480VAC/125VDC operation. Features 10kA rupture capacity and IP20 protection.
Mfr Part #:

4230-T130-K0DE-1A

Mfr Name: ETA
ETA
Thermal-magnetic circuit breaker rated at 1A with 480VAC/125VDC operation. Features 10kA rupture capacity and IP20 protection.
Stock on Request

4230-T130-K0DE-1A Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Voltage Rating

4230-T130-K0DE-1A Description

Short technical summary and product information.

The E-T-A 4230-T130-K0DE-1A is a thermal-magnetic circuit breaker designed for overcurrent protection in industrial and commercial applications. It is rated for 1A continuous current and can operate at voltages up to 480VAC or 125VDC. The breaker offers a high rupture capacity of 10,000 A under UL 489 conditions, with Ics ratings of 7,500 A AC and 10,000 A DC. It is suitable for overvoltage category III environments and has an impulse withstand voltage of 4 kV. The device is rated for pollution degree 3, indicating it can withstand conductive pollution in industrial settings. The IP20 degree of protection provides finger-safe access to terminals. This circuit breaker is typically used in control panels, power distribution systems, and motor protection circuits.

4230-T130-K0DE-1A Quick Information

Product Type: Circuit Breaker
Series: 4230
Canonical Name: 4230-T130-K0DE-1A Thermal-Magnetic Circuit Breaker
Subcategory: Circuit Breakers

4230-T130-K0DE-1A Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

4230-T130-K0DE-1A Features

  • Rated current of 1A.
  • Operates at 480VAC/125VDC.
  • 10kA UL 489 rupture capacity.
  • IP20 finger protection.
  • Overvoltage category III rated.

4230-T130-K0DE-1A Applications

  • Protects cables and motors from overloads.
  • Safeguards industrial process control systems.
  • Used in telecommunications equipment protection.
  • Ideal for power supply circuit protection.
  • Protects computers and peripheral equipment.

4230-T130-K0DE-1A FAQs

7 frequently asked questions generated from this part’s specifications.
What is the rated current of the 4230-T130-K0DE-1A?

The rated current is 1A.

What is the operating voltage range?

It operates at 480VAC and 125VDC.

What is the rupture capacity?

The UL 489 rupture capacity is 10,000 A. The Ics rupture capacity is 7,500 A AC and 10,000 A DC.

What is the overvoltage category?

Overvoltage category III.

What is the impulse withstand voltage?

4 kV.

What is the pollution degree rating?

Pollution degree 3.

What is the degree of protection?

IP20.